張志峰 桂勇華 張福興
摘??要:距離保護是110kV及以下等級輸電線路繼電保護的重要組成部分,在當前復雜的電力網(wǎng)絡環(huán)境下,對促進電網(wǎng)的安全穩(wěn)定運行起到了重要的作用。文章通過對線路距離保護在異常工況下的運行狀態(tài)分析,簡述了距離保護的阻抗繼電器的工作原理,介紹了PT斷線、CT斷線、系統(tǒng)振蕩以及高阻接地等工況下,保護裝置的距離保護可能出現(xiàn)的拒動及誤動情況以及成因。同時,結(jié)合工程實踐經(jīng)驗,針對性提出了一些應用中的處理措施。通過分析,探討線路距離保護裝置實際運行中可能出現(xiàn)故障的分析方法和思路。
關(guān)鍵詞:距離保護;PT斷線;CT斷線;系統(tǒng)振蕩
Abstract:?Distance?protection?is?an?important?part?of?relay?protection?for?110kV?transmission?lines.?In?the?current?complex?power?network?environment,?it?plays?an?important?role?in?promoting?the?safe?and?stable?operation?of?power?grid.?Based?on?the?analysis?of?the?operation?state?of?the?line?distance?protection?under?abnormal?conditions,?this?paper?briefly?describes?the?working?principle?of?the?impedance?relay?of?the?distance?protection,?and?introduces?the?possible?refusal?and?misoperation?of?the?distance?protection?of?the?protection?device?under?the?conditions?of?PT?break,?CT?break,?system?oscillation?and?high?resistance?grounding,?as?well?as?the?causes.?At?the?same?time,?combined?with?practical?engineering?experience,?some?treatment?measures?in?application?are?put?forward.?Through?the?analysis,?this?paper?discusses?the?analysis?methods?and?ideas?of?possible?faults?in?the?actual?operation?of?line?distance?protection?device.
Keywords:?distance?protection;PT?break;?CT?break;?system?oscillation
輸電線路的距離保護由于不受系統(tǒng)運行方式變化的影響,所以在110kV及以下電壓等級的較復雜的電力網(wǎng)絡,可以作為一種主要的輸電線路線繼電保護配置。在距離保護中,阻抗繼電器(或稱阻抗元件)通過測量故障電壓和故障電流計算保護安裝點到線路故障點至的阻抗。在實際工程實踐中,由于工頻電壓、電流量受到各種因素的擾動,導致測量阻抗偏離實際值,引起距離保護中阻抗元件誤判,需要在距離保護裝置設計時進行針對性處理,提高裝置的可靠性。
1?距離保護的阻抗分析
距離保護裝置通常配置了三段相間距離和三段接地距離繼電器。
對于接地距離保護,其測量阻抗可以通過下式計算:
式中為零序補償系數(shù),反應非故障相零序電流產(chǎn)生的互感磁場對故障相的影響,與正序阻抗和零序阻抗有關(guān),其計算公式為:
對于相間距離保護,其測量阻抗可以通過下式計算:
在正常工況下,當線路上發(fā)生故障,保護安裝處測得的電流包含了線路的負荷電流和故障電流兩個部分,據(jù)此計算的測量阻抗能夠正確反應故障點與保護安裝處之間的阻抗,從而準確定位故障的距離。