摘要:風(fēng)電場風(fēng)機(jī)側(cè)升壓變壓器是風(fēng)電場電力系統(tǒng)的重要組成部分。韓國分布式能源對于風(fēng)機(jī)直接并網(wǎng)的特殊規(guī)定決定了必須選擇特殊配置的中壓變壓器來符合當(dāng)?shù)仉娋W(wǎng)要求.而中壓線路短路電流的設(shè)計(jì)計(jì)算就是變壓器選型中安全性的重要因素.?通過科學(xué)合理的短路電流較核計(jì)算,不僅能在滿足安全可靠的前提下經(jīng)濟(jì)地選擇合適的設(shè)備,?也為整個(gè)風(fēng)電項(xiàng)目合理配置做出貢獻(xiàn).?并且有利于我們對周邊國家相關(guān)電力工程熟悉當(dāng)?shù)匾蠛头e累經(jīng)驗(yàn),完善并提高自身技術(shù)水平。
關(guān)鍵詞:風(fēng)電 安全 變壓器?短路電流?校核
Abstract:?The step up Transformer of wind turbine is the important components of wind power electric system. The special MV transformer configuration to meet the requirement from local utility according special grid connection regulation of Korea distribution power system. The design calculation of short circuit is one of important factor for transformer safety configuration. By reasonable short circuit calculation and validation, not only suitable to select equipment with economic and safety, but also contributed for the whole wind project better configuration. Also have benefit to know the local requirement and accumulate experience, enhance and improve our technical capability.
Key words:?Wind Power, Safety, Transformer, Short Circuit, Validaiton
1 引言
韓國屬于東亞的發(fā)達(dá)國家,其經(jīng)濟(jì)發(fā)展尤其是工程項(xiàng)目有很強(qiáng)的規(guī)范性。隨著國家“一帶一路”戰(zhàn)略的實(shí)施,我們也于2019年參與了韓國的風(fēng)力發(fā)電工程項(xiàng)目。值得一提的是,本文所述的韓國的風(fēng)電工程(簡稱CS項(xiàng)目)本身就是一個(gè)分布式電力項(xiàng)目,它位于韓國東南部慶尚北道,離浦項(xiàng)約60KM。項(xiàng)目由韓國DAEMYOUNG公司開發(fā),設(shè)計(jì)容量20MW,配置6臺西門子歌美颯SWT-3.2-113M直驅(qū)風(fēng)機(jī)。
CS項(xiàng)目位于韓國東部山區(qū),道路崎嶇且受環(huán)保約束不宜做大規(guī)模開發(fā)。當(dāng)?shù)卣囊?guī)劃是因地制宜地分散開發(fā)一些小的電力項(xiàng)目,再集中到大的升壓站輸送到骨干電網(wǎng)。比如CS項(xiàng)目的6臺風(fēng)機(jī)之間用埋地電纜連接,線路終端再通過項(xiàng)目的開關(guān)站直接并到22.9kV中壓架空線路,最后連接到20多公里外的GIS升壓站連接到154kV的大電網(wǎng)。韓國本地電網(wǎng)的特殊要求是風(fēng)機(jī)出口并網(wǎng)必須采用Y-Y(星-星)連接,因?yàn)橹袎弘娋W(wǎng)就是Y-Y連接,任何設(shè)施直連中壓電網(wǎng)必須要滿足其電壓、頻率等特性完全匹配。而通常的風(fēng)機(jī)側(cè)變壓器繞組設(shè)計(jì)一般采用Y-△(星-三角)連接,主要考慮是把諧波消除在三角形連接的繞組中,這樣對風(fēng)機(jī)和對電網(wǎng)都是一種保護(hù)。西門子歌美颯公司應(yīng)對客戶的特殊需求,提出了兩種應(yīng)對方案:一是改造原先塔筒內(nèi)的變壓器,從Y-△變成Y-Y;二是把變壓器和環(huán)網(wǎng)柜放置在塔外形成安全的升壓開關(guān)亭,外置變壓器直接采用Y-Y。由于原裝變壓器是在歐洲工廠生產(chǎn),改造費(fèi)用高昂,經(jīng)實(shí)地考察,最終與韓國本地知名的電氣工程公司LSIS合作,采購LS設(shè)計(jì)生產(chǎn)的Ynyn0d11變壓器,并配合韓國電網(wǎng)的試驗(yàn)要求,滿足了項(xiàng)目業(yè)主和當(dāng)?shù)仉娋W(wǎng)的所有需求。
電氣系統(tǒng)的設(shè)計(jì)及選型涉及到很多復(fù)雜計(jì)算,安全性上的一個(gè)核心指標(biāo)就是短路電流的計(jì)算。本文對于具體的變壓器設(shè)計(jì)和施工不再詳述,重點(diǎn)討論工程設(shè)計(jì)中電力系統(tǒng)的短路電流的計(jì)算和校核,從安全性上保證我們的設(shè)備選型的科學(xué)合理,同時(shí)滿足當(dāng)?shù)仉娋W(wǎng)的特殊要求。經(jīng)過比對韓國現(xiàn)行的電網(wǎng)標(biāo)準(zhǔn),我們發(fā)現(xiàn)它基本匹配國際IEC標(biāo)準(zhǔn)。比如對于系統(tǒng)短路電流計(jì)算,IEC60969都通用于本地要求。
2 系統(tǒng)參數(shù)計(jì)算及假設(shè)
首先,我們選取系統(tǒng)單線圖(見后圖1).
通過研究CS項(xiàng)目的電氣系統(tǒng)單線圖,我們得知遠(yuǎn)端匯流站及系統(tǒng)基本參數(shù)如下:
基準(zhǔn)容量:Sj = 100 MVA;高壓側(cè)(154kV)基準(zhǔn)電壓:U1j = 154 kV;中壓側(cè)(22.9kV)基準(zhǔn)電壓:U2j = 22.9 kV;基準(zhǔn)電壓:U3j = 22.9 kV。
短路節(jié)點(diǎn)的短路電流計(jì)算時(shí)間t都設(shè)為0秒。
系統(tǒng)編號從XT1到XT6是系統(tǒng)中各風(fēng)機(jī)及電氣設(shè)備節(jié)點(diǎn),其單相短路容量:= 3.2?MVA;而編號xt1為網(wǎng)側(cè)節(jié)點(diǎn),其單相短路容量:
= 1e+008 MVA。
對于雙繞組變壓器,編號ZB0為遠(yuǎn)端匯流站升壓變,其電壓:154/22.9?kV,型號:S/S MTR,額定容量:Se = 45000?MVA,短路電壓百分比:Ud%?= 10.5,中性點(diǎn)接地電阻未知,正序阻抗標(biāo)么值:= 0.2333,零序阻抗標(biāo)么值:=0;
風(fēng)機(jī)側(cè)變壓器編號從ZB1到ZB6,電壓:22.9/0.69?kV,型號:DKCS-1200/10.5-200/0.1,額定容量:Se = 3400?MVA,短路電壓百分比:Ud%?= 7,中性點(diǎn)接地電阻Z未知,正序阻抗標(biāo)么值:= 2.0588,零序阻抗標(biāo)么值都等于0。
對于線路,編號為L1的特指從風(fēng)場到匯流站的外部線路。電壓:Ue = 154?kV,型號:2xLGJ-400/20+4xLJ-185,截面:S = 400?mm2,根數(shù):n = 1,正序阻抗:X1?= 0.4Ω/km,零序阻抗:X0?= 1.4Ω/km,X0/X1:3.5,長度:L = 25?km,正序阻抗標(biāo)么值:= 0.0422,零序阻抗標(biāo)么值:
= 0.1476。
3 短路電流計(jì)算
首先我們繪出系統(tǒng)等值簡化阻抗圖(見后圖2,3,4)。
4?結(jié)論
(1)分析了韓國風(fēng)電項(xiàng)目分布式能源的具體要求。詳細(xì)對電力系統(tǒng)的短路電流計(jì)算進(jìn)行了驗(yàn)證。
(2)經(jīng)驗(yàn)算,CS項(xiàng)目154kV側(cè)三相短路電流為11.744kA,單相短路電流為6.379kA。22.9kV側(cè)三相短路電流為12.601kA,單相短路電流為1.633kA。在和韓國業(yè)主和本地供應(yīng)商LS充分溝通后,CS項(xiàng)目22.9kV側(cè)設(shè)備短路電流水平按21kA進(jìn)行電氣選擇,這也是韓國常規(guī)中壓設(shè)備短路電流的常用配置,完全滿足本工程要求。
(3)綜合來說,LS該款變壓器針對韓國用戶的特殊的要求,在安全性保障方面很好地滿足了可靠性及經(jīng)濟(jì)性的需求,對于日后韓國類似工程起到了范本效用。
參考文獻(xiàn)
[1] 楊彬,同向前,劉健,等.含分布式電源配電網(wǎng)的短路電流計(jì)算方法研究?[J].電網(wǎng)技術(shù),2015,39(7):1977-1982.
[2] Insu Kim. Steady‐state short‐circuit current calculation for internally limited inverter‐based distributed generation sources connected as current sources using the sequence method [J].WILEY. International Transactions on Electrical Energy Systems,?2019, 10.1002/2050-7038.12125:1-16.
[3] 陳紅梅.220kV智能變電站電氣設(shè)計(jì) [D].哈爾濱 哈爾濱工業(yè)大學(xué),2015.
[4] 候世勇,董景義,李杰.?變壓器短路電流分析計(jì)算?[J].變壓器,2012,49(10):1-6.
[5] 鞠偉.大安中廣核安廣風(fēng)電場電氣一次系統(tǒng)研究及設(shè)計(jì) [D].長春 長春工業(yè)大學(xué),2018.
[6] 李龍女,張雅倩,李巖,等.帶平衡繞組的分列式變壓器短路電流計(jì)算分析?[J].電力系統(tǒng)及其自動化學(xué)報(bào),2019,31(3),69-75.
[7] 楊金剛,何成明,李順昕,等.短路電流計(jì)算外網(wǎng)等值方法研究及應(yīng)用?[J].中國電力,2018,51(12),56-62.
[8] 熊友紅,邱軍,趙建剛,等.短路電流計(jì)算在電力系統(tǒng)事故分析中的應(yīng)用?[J].冶金動力,2020,241(3),8-11.
[9] 王寓,王主丁,張宗益,等.國內(nèi)外常用短路電流計(jì)算標(biāo)準(zhǔn)和方法的比較研究?[J].電力系統(tǒng)保護(hù)與控制,2010,38(20),148-152.
[10] 黃冠標(biāo).基于IEC60909標(biāo)準(zhǔn)的短路電流計(jì)算軟件設(shè)計(jì) [D].廣州 華南理工大學(xué),2015.
[11]?肖鑫鑫.計(jì)及分布式電源的配網(wǎng)潮流和短路電流計(jì)算研究 [D].上海 上海交通大學(xué)電子信息與電氣工程學(xué)院,?2008.
[12] 陳博,邱建,曾耿暉,等.計(jì)及阻抗匹配平衡牽引變壓器的電網(wǎng)短路計(jì)算方法?[J].電力系統(tǒng)保護(hù)與控制,2016,44(13),33-39.
[13] Energy - Wind Farms; Researchers from Hohai University Report Findings in Wind Farms (A Practical Short-circuit Current Calculation Method for Dfig-based Wind Farm Considering Voltage Distribution) [J]. Energy Weekly News,2019.
[14] 邱麗萍,張彥濤,王蒙,等.適用于交流長線路的動態(tài)相量時(shí)域短路計(jì)算方法研究?[J].中國電機(jī)工程學(xué)報(bào),2019,39(13),3736-3743.
作者簡介:羅斌 男,(1975-),男,工程師,碩士。研究方向:新能源能電力工程。