李承昊 王悅 張國毅
摘 要:該文根據(jù)現(xiàn)行國家標(biāo)準(zhǔn),以沈陽某超高商業(yè)大廈的使用性質(zhì)、建筑用途、建筑特征、周邊環(huán)境等綜合數(shù)據(jù)為基礎(chǔ),分析該建筑的雷擊損害類型、雷擊風(fēng)險(xiǎn)分量、建筑物及入戶設(shè)施的截收面積、年預(yù)計(jì)雷擊次數(shù)等關(guān)鍵參數(shù),進(jìn)而研究超高建筑的雷擊風(fēng)險(xiǎn)分布特征,以期對(duì)超高建筑的防雷設(shè)計(jì)、施工等工作提供參考意見。
關(guān)鍵詞:超高建筑 雷擊風(fēng)險(xiǎn)分量 風(fēng)險(xiǎn)分布特征
中圖分類號(hào):TU972.4 文獻(xiàn)標(biāo)識(shí)碼:A 文章編號(hào):1674-098X(2016)07(a)-0080-02
Analysis of Characteristics of Ultra-high Commercial Building Lightning Risk Distribution
Li Chenghao Wang Yue Zhang Guoyi
Liaoning Lightning Protection Technical Service Center,Shenyang Liaoning,110010, China)
Abstract:In this paper, according to the current national standard, the use of a high commercial building in shenyang properties, USES and architectural features, environment and other comprehensive data as the foundation, analysis of the construction of lightning damage type, lightning strike risk component, buildings and household facilities JieShou area, lightning frequency that key parameters, such as further study of supertall buildings lightning risk distribution characteristics, in order to ultrahigh construction of lightning protection for reference to design, construction,etc.
Key Words:Ultra-high buildings; Lightning strike risk weight; Risk distribution characteristics
文章所分析的建筑物位于沈陽市中心,建筑長50 m,寬48 m,高350 m,為沈陽標(biāo)志性建筑。該建筑入戶電纜均為埋地敷設(shè),由市電直接引入樓內(nèi)變電室,建筑物內(nèi)外常年有人員活動(dòng),年雷暴日26.9 d,土壤電阻率實(shí)測113.28 Ω·m,消防設(shè)施包括人工和自動(dòng)滅火裝置,下面對(duì)該建筑的雷擊風(fēng)險(xiǎn)進(jìn)行詳細(xì)計(jì)算分析。
1 雷擊風(fēng)險(xiǎn)分量的鑒別
1.1 雷擊損害類型的鑒別
該建筑屬于商業(yè)建筑,遭受雷電閃擊造成的損失主要是人員生命的損失和經(jīng)濟(jì)損失,因雷擊電源停電等造成的公眾服務(wù)的損失可忽略不計(jì),社會(huì)文化遺產(chǎn)的損失不存在,因此,該建筑地塊只需計(jì)算人員生命的損失風(fēng)險(xiǎn)R1。
1.2 雷擊風(fēng)險(xiǎn)分量的鑒別
雷擊該建筑時(shí),R1型風(fēng)險(xiǎn)存在的風(fēng)險(xiǎn)分量分析如下:
當(dāng)雷電閃擊建筑附近或服務(wù)設(shè)施及其附近時(shí),以及雷擊建筑物附近時(shí)所產(chǎn)生的感應(yīng)磁場變化,不足以威脅到人員生命安全,因此,該次所計(jì)算的分量包括RA、RB、RU、RV,RC、RM、RW、RZ風(fēng)險(xiǎn)分量記為0。
2 雷擊風(fēng)險(xiǎn)分量的計(jì)算
2.1 建筑物及入戶設(shè)施的截收面積
2.1.1 每年的截收閃電面積
Ad=L·W+6H(L+W)+9π(H)2
=48×50+6×350×(48+50)+9×3.14×350×350
=3671805.84(m2)
2.1.2 附近地面的截收閃電面積
AM=L·W+2×250(L+W)+π(250)2
=48×50+2×250(48+50)+π(250)2
=247770.38(m2)
2.1.3 入戶電力線纜的截收閃電面積
Al=[Lc-3(Ha+Hb)]
=0.00(m2)
2.1.4 入戶電力線纜附近地面的截收面積
Ai=25LC×ρ0.5
=25×1000×113.280.5
=266082.69(m2)
2.1.5 入戶通信線纜的截收閃電面積(埋地)
Al=ρ0.5[Lc-3(Ha+Hb)]
=0.00(m2)
2.1.6 入戶通信線纜的截收閃電面積(埋地)
Ai=25LC×ρ0.5
=25×1000×113.280.5
=266082.69(m2)
2.1.7 入戶電力線纜服務(wù)設(shè)施a的截收面積
Ada=La·Wa+6Ha(La+Wa)+9π(Ha)
=0.00(m2)
2.1.8 入戶通信線纜服務(wù)設(shè)施a的截收面積
Ada=La·Wa+6Ha·(La+Wa)+9π(Ha)
=0.00 (m2)
2.2 年預(yù)計(jì)雷擊次數(shù)
2.2.1 建筑物年預(yù)計(jì)雷擊次數(shù)
ND=NgAdCd×10-6
=2.69×3671805.84×0.5×10-6
=4.9386(次/年)
2.2.2 附近地面的年預(yù)計(jì)雷擊次數(shù)為
Nm=Ng(Am-AdCd)×10-6
=2.69×(247770.375-3671805.842×0.5)×10-6
=0.0000(次/年)
2.2.3 入戶供電線纜的年預(yù)計(jì)雷擊次數(shù)為
NL=NgAlCdCt×10-6
=2.69×0.00×0.5×0.2×10-6
=0.0000(次/年)
2.2.4 入戶供電線纜附近預(yù)計(jì)雷年預(yù)計(jì)閃擊次數(shù)為
NI=NgAiCeCt×10-6
=2.69×266082.69×0.1×0.2×10-6
=0.0143(次/年)
2.2.5 入戶通信線纜的年預(yù)計(jì)雷擊次數(shù)為
NL=NgAlCdCt×10-6
=2.69×0.00×0.5×1×10-6
=0.0000 (次/年)
2.2.6 入戶通信線纜附近預(yù)計(jì)雷年預(yù)計(jì)閃擊次數(shù)為
NI=NgAiCeCt×10-6
=2.69×266082.69×0.1×1×10-6
=0.0716 (次/年)
2.2.7 附近供電服務(wù)設(shè)施的年預(yù)計(jì)雷擊次數(shù)為
NL=NgAlCdCt×10-6
=2.69×0.00×0.5×10-6
=0.0000(次/年)
2.2.8 附近通信服務(wù)設(shè)施的預(yù)計(jì)雷年預(yù)計(jì)閃擊次數(shù)為
NI=NgAiCeCt×10-6
=2.69×0.00×0.5×10-6
=0.0000(次/年)
年預(yù)計(jì)雷擊次數(shù)鑒別:
綜合以上計(jì)算結(jié)果,該建筑各系統(tǒng)年預(yù)計(jì)危險(xiǎn)次數(shù)見表1。
由表1可以看出,超高建筑可能發(fā)生的雷擊主要集中在樓體直接接閃的情況下,由于電力和通信線纜均埋地敷設(shè),所以入戶設(shè)施的雷擊概率主要集中在感應(yīng)雷擊,但所占比重很小,不足2%。
3 人員傷亡損失的風(fēng)險(xiǎn)
3.1 該建筑人員傷亡損失量值
Lt和Lf的值由于確定困難,故均取典型平均值。
Lt的取值如下。
建筑物外部3 m內(nèi)區(qū)域:Lt=10-2
建筑物內(nèi)部區(qū)域:Lt=10-4
建筑物L(fēng)f的取值:Lf=10-1
建筑物內(nèi)部系統(tǒng)不會(huì)立即危及人員生命,故L0的取值:L0=0
3.2 該建筑項(xiàng)目風(fēng)險(xiǎn)分量計(jì)算
將此文的以上計(jì)算結(jié)果帶入表2公式中,得出R1型風(fēng)險(xiǎn)分量的數(shù)值及所占百分比如表2所示。
通過表2數(shù)據(jù)可以看出,由直接雷擊引起的跨步電壓、接觸電壓的RA風(fēng)險(xiǎn)分量占據(jù)71.37%,由直接雷擊引起的二次傷害RB風(fēng)險(xiǎn)分量占據(jù)28.55%,這兩項(xiàng)表明直接雷擊引起的風(fēng)險(xiǎn)分量占據(jù)總風(fēng)險(xiǎn)的99.2%,對(duì)照表1直接雷擊大樓的概率98.29%,可以看出雷擊風(fēng)險(xiǎn)是與雷擊概率成正比的非線性關(guān)系。
4 結(jié)語
通過文章上述分析,超高建筑的主要雷擊風(fēng)險(xiǎn)來源是直擊雷,包括雷擊樓頂和雷擊樓體側(cè)面,由于距離地面更高而有更大概率優(yōu)先接閃閃電向下先導(dǎo)電流,在防雷設(shè)計(jì)與施工中應(yīng)更加注重天面外邊沿的防護(hù),防止因雷擊導(dǎo)致混凝土塊等物體的墜落,同時(shí)加強(qiáng)高樓層金屬門窗的等電位連接,并每隔一層或兩層安裝均壓環(huán),防止雷擊樓體側(cè)面導(dǎo)致異物的脫落。
參考文獻(xiàn)
[1] 陳渭民.雷電學(xué)原理[M].北京:氣象出版社,2003.
[2] GB/T 21714.2-2015,雷電防護(hù)第2部分:風(fēng)險(xiǎn)管理[S].
[3] 楊仲江.雷電災(zāi)害風(fēng)險(xiǎn)評(píng)估與管理基礎(chǔ)[M].氣象出版社,2009.