        Adaptive Robust Control of Multi-Machine Power Systems with Control Time Delay

        2018-07-14 07:22:06ZhongqiangWuFengLiChunqiDuandWeiZhang

        Zhongqiang Wu, Feng Li, Chunqi Du and Wei Zhang

        (Key Lab of Industrial Computer Control Engineering of Hebei Province, College of Electrical Engineering,Yanshan University, Qinhuangdao 066004, Hebei, China)

        Abstract: The adaptive H∞ control problem of multi-machine power system in the case of disturbances and uncertain parameters is discussed, based on a Hamiltonian model. Considered the effect of time delay during control and transmission, a Hamilton model with control time delay is established. Lyapunov-Krasovskii function is selected, and a controller which makes the system asymptotically stable is got. The controller not only achieves the stability control for nonlinear systems with time delay, but also has the ability to suppress the external disturbances and adaptive ability to system parameter perturbation. The simulation results show the effect of the controller.

        Keywords: multi machine power systems; time delay; H∞ control; uncertain parameters; disturbance

        1 Introduction

        Power systems are electrical energy productions and consumption systems composed of power generations, substations, transmissions, and the users. It has an indispensable position in the national economy, defense construction and other fields[1]. Two basic conditions must be met in the safe operation of the power system: first, all electrical equipment are in the normal state and meet the variety of operating condition; second, system voltage and frequency should be kept within the scope of the provisions, which requires all generators to maintain synchronous operation[2]. The operation state of power system directly affects the actual safety level of system. Therefore, it is necessary to pay attention to the control problem of safe operation, in order to enhance the reliability of power supply system. The safe control for power system is that all kinds of control measures and methods are taken to make the power system operate in the normal state. In Ref.[3], a large scale power blackout in the domestic and foreign is taken as an example, the security and stability control of power system is proposed based on system response, and the key technology and new research is discussed[4-8].

        After years of research and development,a variety of control methods, such as robust control, adaptive control, fuzzy control, neural network and genetic algorithm have been applied to the power system[9-11]. In Ref.[12], based on the robust nonlinear control theory, the stability of ship power system containing the propulsion load is analyzed, and the nonlinear control of the ship power system is discussed, in order to enhance the dynamic quality of ship power system. Considered the variable coupling relationship of ship power system, the controller can effectively restrain the influence of the disturbance on the power-angle and the frequency of generator. For the large load of ship electric power system, taking into account the nonlinear impact of the load to the grid some limitations are brought into the design of controller. In Ref.[13], a nonlinear robust adaptive controller is designed to reduce the influence of the interference on the power-angle and the frequency of multi machine power system considered the parameter uncertainty of reactance. In Ref.[14], a robust adaptive excitation controller is designed based onL2interference suppression theory of the multi machine power system containing uncertain parameters. In Ref.[15], a kind of intelligent power system stabilizer based on fuzzy control is proposed, it has the advantages that the control can be selected according to the actual operation conditions of power systems, but the fuzzy control rule is needed to be determined by the operation experience, so that in order to carry out fuzzy reasoning and decision, designers need have a certain operation experience of power system. In Ref.[16], a design method based on maximum entropy principle to optimize fuzzy neural network is put forward to realize stable control of power system. However the demand to choose the center parameters of the membership function is high in the scheme, if the center parameters of the membership function are not selected properly, it will affect the learning effect. A fuzzy power system controller adopted genetic algorithm is proposed in Refs.[17-18]. Genetic algorithm is introduced into the design of fuzzy logic controller, which enhances the dynamic performance of system significantly, and it has a good robustness under small disturbance signal. However the overshoot of the system is a little larger, and the transition time is a little longer.

        Hamilton system is a kind of conservative nonlinear system derived from classical mechanics, which is one of the important research fields in nonlinear science, and has certain advantages in engineering application. Lyapunov function based on Energy is selected from the Hamilton function of the generalized Hamilton system, so the key problem to solve the nonlinear system with the energy function is that the nonlinear system is translated into a dissipative Hamilton function. The research on generalized Hamilton system in the nonlinear control field of power system is developing rapidly. The Ref.[19] based on the transient energy function of power system, presents a new Lyapunov function. The function is used to stabilize the power system, and the mutual influence among the dynamic processes of generator is considered in the design of the controller, but the external disturbances and load changes have not been discussed. In Ref.[20], it is pointed out that the influence of load nonlinearity must be considered for the control of power system. In Ref.[21], a wide area time-delay damping control of multi machine power system is studied. The stable control of wide area nonlinear power system with transmission signal delay is analyzed by the dissipative Hamiltonian system method. However the adaptive control for power systems with interferences and uncertain parameters is not considered.

        In the paper, a Hamilton model with control delay is established for multi machine power system, considered time delay in transmission process. By constructed a Lyapunov-Krasovskii function, an adaptiveH∞control scheme is designed based on Hamilton function, and the stable control is achieved for nonlinear power system with time-delay, disturbance and uncertain parameters.H∞control can restrain the disturbance and the influence of uncertain parameters in the system is overcome by adaptive control. Simulation results show the effective of the control scheme.

        2 The Model of Multi-Machine Power System and its Hamilton Model

        The power system which is composed ofninterconnected generators is considered as follows. Each generator is expressed by a three-order system.

        (1)

        The Hamilton function of system (1) can be selected as Ref.[2]: The dynamic equation as follows:

        (2)

        where

        qi=

        Eq.(2) is written as follows:

        (3)

        Eq.(3) is a kind of dissipative Hamilton form.

        3 Adaptive H Control with Time Delay

        3.1 The Establishment of Hamilton Model with Time Delay

        Taking 2 machine systems as an example, the Hamilton model with time delay is set up and also can be extended to the multi-machine system. The Hamilton model of 2 machine systems as follows:

        (4)

        In the practical system, the feedback control signal of different regions usually has time delay (it is caused by feedback signal transmission, especially for long distant regions), and the feedback control with time delay can be expressed as:

        (5)

        wherev1,v2are the controller composed of the local state variables, used to design an adaptive controller.K12,K21is feedback gain of feedback control signal for different regions.τis transmission time delay. The time delay of state transfer between different regions is:

        Introducing Eq.(5) into Eq.(4):

        (6)

        Eq.(6) is denoted as follows:

        (7)

        where

        Multi-machine power system is also obtained as the form of Eq.(7). For convenience hereinafter, the Eq.(7) can be rewritten as follows:

        (8)

        wherexτ=x(t-τ).

        3.2 Adaptive H Controller Design

        Considered external perturbation and parameter perturbation,the adaptiveH∞control scheme of system (8) is designed. The parameter perturbation of system is small, so that the dissipation of the system is not changed. The Eq.(8) is expressed as a system with unknown constant vectorp.

        (9)

        whereyis the output;wis the disturbance input;zis the penalty signal;dis disturbance input matrix;ris the weighted matrix which the column is full rank.

        The adaptiveHcontrol problems of system (9) are described as following: an interference attenuation level is givenγ>0, to find a state feedback controller:

        (10)

        It will made theL2gain (fromwtoz) of the closed-loop system less than or equal toγas follows.

        (11)

        The closed loop system under the control scheme (10) is asymptotically stable whenw=0.

        Various items of uncertain parameters in the system (9) can be further written as:

        J(x,p)=ΔJ(x,p)+J(x)

        R(x,p)=ΔR(x,p)+R(x)

        whereΔJ(x,p), andΔR(x,p) are uncertainties.

        To facilitate the design of adaptiveHcontroller, some assumptions are given:

        Assumption1There exists a suitable dimension matrixΨ(x) so that

        [J(x,p)-R(x,p)]ΔH(x,p)=gΨT(x)θ

        (12)

        where,θis a constant vector aboutp. Assumption 1 is called the matching condition and it is also a general assumption in the Hamilton system control. In most cases, there are suchΨ(x) andθ, making the Eq.(12) be true.

        Assumption2R(x,p)≥A,A≥0 is a constant matrix.

        Considering system (9), and supposing assumption 1 and 2 satisfied, if there are matricesP=PT>0,Q=QT>0,Γ=ΓT>0 such that

        (13)

        where * represents symmetric term, and

        (14)

        ProofIntroducing Eq.(12) and Eq.(14) into Eq.(9)

        (15)

        The Lyapunov-Krasovskii function is chosen as follows:

        (16)

        The derivative ofV(x,xτ,θ) to time is calculated as follows:

        ggT(P+Q)-P]H(x)+TH(x)TH(xτ)-

        (17)

        whereξ(t)=[TH(x),TH(xτ),ωT]T, from inequality(13)Λ<0,it can be seen that:

        (18)

        The Eq.(9) indicates that the asymptotically stability is achieved.

        4 Simulation Study

        The simulation research for double machine power system is done. Select generator parameters:

        M1=23.64 s,M2=6.4 s,xd1=0.146 p.u.,

        D1=0.31 p.u.,D2=0.535 p.u.,Pm1=0.7157 p.u.,

        Assuming that the uncertain parameters as follows:

        Let

        It is easy to test that Assumption 1 is satisfied.

        After many tests,let

        K12=25,K21=1,Γ=1

        Fig.1 The power angle response curve of generator

        Fig.2Therotorangularvelocityresponsecurveofthefirstgenerator

        Fig.3Therotorangularvelocityresponsecurveofthesecondgenerator

        Fig.4Theq-axistransientpotentialresponsecurveofthefirstgenerator

        Fig.5Theq-axistransientpotentialresponsecurveofthesecondgenerator

        The goal of power system transient stability control is to make each generator tend to the rated synchronous speed[22]. As can be seen from the simulation results shown in Figs.1-5, after a period of adjustment, the system can reach a stable operating point again. The difference of angular speed and synchronous speed of generator converges to zero, and the rotor running angle of each generator converges to a fixed angle, and the stability is good. The system has a strong robustness to external disturbance, and the ideal control effect is obtained.

        In order to test the control effect, the controller designed in this paper is compared with the controller based on DIEB (Damping Injection Energy Balancing) in Ref.[19].

        Comparing Fig.1 and Fig.6, it can be seen that the turbulence amplitude in the paper is less than that in Ref.[19], and the response time is also less than that in Ref.[19]. The controller designed in the paper is better than that in Ref.[19].

        Fig.6ThepowerangleresponsecurvebythemethodinRef.[19]

        To verify the adaptive ability of power system, the parameter variations of power system are considered. Let

        Fig.7 The power angle response curve of generator

        Fig.8Therotorangularvelocityresponsecurveofthefirstgenerator

        As can be seen from Figs.6-10, the controller has a strong adaptive ability to the parameter perturbation of system. When the system parameters have changed, the system tends to be stable, and the good control effect is obtained.

        Fig.9Therotorangularvelocityresponsecurveofthesecondgenerator

        Fig.10Theq-axistransientpotentialresponsecurveofthefirstgenerator

        Fig.11Theq-axistransientpotentialresponsecurveofthesecondgenerator

        5 Conclusions

        In this paper, the adaptiveH∞control scheme of multi-machine power system with control time delay and parameter uncertainty is studied based on Hamiltonian function. Considered the time delay effect in the transmission process of control, a Hamilton model with control delay is established. Selected the appropriate Lyapunov-Krasovskii function, an adaptive robustH∞state feedback control law is derived which can guarantee the asymptotic stability of the system.H∞controller can realize the disturbance suppression, and adaptive control can improve the robustness of system to uncertain parameters. The simulation results show that the designed controller makes the power system to be stable, and the effect of the proposed controller is tested.

        国产99久久久国产精品免费| 国产精品久久国产精品99| 亚洲av综合永久无码精品天堂 | 一区二区三区内射视频在线观看 | 亚洲AV无码专区国产H小说| 亚洲啊啊啊一区二区三区| 国产免费一区二区三区在线视频| 二区三区日本高清视频| 亚洲av无码精品无码麻豆| 欧美人与禽2o2o性论交| 变态 另类 欧美 大码 日韩 | 日日噜噜夜夜狠狠久久无码区 | 国产av无码专区亚洲av极速版| 97超级碰碰人妻中文字幕| 日韩丝袜亚洲国产欧美一区| 国产青青草视频在线播放| 国产自拍视频一区在线| 美利坚日韩av手机在线| 中文字幕日韩欧美一区二区三区 | 99成人无码精品视频| 中文字幕乱码琪琪一区| 日韩一区二区三区熟女| av区无码字幕中文色| 久久超碰97人人做人人爱| 初尝黑人巨砲波多野结衣| 伊人久久亚洲综合影院首页| 亚洲成片在线看一区二区| 国家一级内射高清视频| 日本强伦姧人妻一区二区| 国产av一区二区三区传媒| 初尝黑人巨砲波多野结衣| 免费二级毛片在线播放| 成人偷拍自拍在线视频| 国产在线观看视频一区二区三区| 精品福利一区二区三区免费视频 | 亚洲av之男人的天堂| 九九99久久精品在免费线97| 成人亚洲av网站在线看| 视频在线观看一区二区三区| 正在播放老肥熟妇露脸| 久久无码av三级|